Factory-assembled active harmonic filter cabinets built with Forte GRIDVAR AHF modules. Available in three performance tiers — Standard (GRIDVAR-G), Compact (GRIDVAR-C) and Premium SiC (GRIDVAR-X). Same hardware platform as SVG panels — different firmware and control card for dedicated harmonic filtering.
Forte AHF Panels are factory-assembled active harmonic filter cabinets — each built around one of three GRIDVAR AHF module tiers. The physical panel platform is identical to SVG panels: CT, main breaker, HMI, controller and all internal wiring are common. The difference is in the control card and firmware — optimized for dedicated harmonic filtering rather than reactive power compensation.
GRIDVAR-G AHF — Standard Series. 2nd–51st harmonic, 220V–690V, up to 200A/module. Cost-effective filtering for general industrial harmonic problems.
GRIDVAR-C AHF — Compact Series. 2nd–51st harmonic, 400V, up to 150A. Ultra-slim modules for maximum cabinet density.
GRIDVAR-X AHF — Premium SiC Series. 2nd–51st harmonic, 220V–380V, 4µs response. For arc furnaces and extreme harmonic environments.
All three AHF panel types reduce THDi to below 5% at the point of common coupling, meeting IEEE 519 and IEC 61000-3-4 requirements. Each harmonic order can be individually prioritised for selective filtering. Multiple cabinets operate in parallel for higher capacity. Factory tested, shipped complete, ready for connection.
All three panels share the same cabinet platform. The AHF module determines harmonic filtering performance.
| Parametre | GRIDVAR-G AHF | GRIDVAR-C AHF | GRIDVAR-X AHF |
|---|---|---|---|
| Series | Standard | Compact | Premium SiC |
| Switching technology | Advanced IGBT, 3-Level | High-Density IGBT, 3-Level | SiC MOSFET, 3-Level |
| Çalışma gerilimi | 220V / 400V / 480V / 690V | 400V (-15%~+15%) | 220V – 380V |
| Modül kapasitesi (A) | 15 · 25 · 30 · 50 · 75 · 100 · 125 · 150 · 200 A | 30 · 50 · 75 · 100 · 150 A (220A PRO) | 20 · 35 · 50 · 75 · 100 · 200 A |
| Tepki süresi | ≤ 50 µs / ≤ 5 ms total | ≤ 10 ms | 4 µs / ¼ cycle (harmonic) |
| Harmonik filtreleme aralığı | 2nd – 51st | 2nd – 51st | 2nd – 51st |
| Anahtarlama frekansı | 25.6 kHz | 20 kHz | > 100 kHz |
| THDi reduction | < 5% at PCC | < 5% at PCC | < 5% at PCC |
| Selective filtering | Yes — individual harmonic priority | Yes — individual harmonic priority | Yes — individual harmonic priority |
| Maks. paralel modül | 20 modules | 20 modules | 10 modules (smart rotation) |
| Çalışma sıcaklığı | −20°C ~ +55°C | −25°C ~ +55°C | −25°C ~ +55°C |
| Sistem verimliliği | ≥ 98% | ≥ 97.5% | ≥ 98% |
| Filtreleme etkinliği | ≥ 98% | > 95% | ≥ 98% |
| 3-Phase balancing | Yes (Active) | Yes (Active) | Yes (Active) |
| Overload | Auto-limited at 100% rated capacity | Auto-limited at 100% rated capacity | 110% Continuous |
| Communication | RS485, CAN Bus, Modbus RTU, Mobile APP, Optional HMI | RS485 / CAN, Optional HMI | Bluetooth / Mobile APP, RS485 / CAN / RJ45 |
| IP Protection | IP20~IP54 | IP20 | IP20 |
| Best for | General industry, 690V plants | Retrofit, tight spaces, broad filtering | Arc furnaces, steel, extreme harmonics |
These features are standard across all three AHF Panel types.
| Parametre | Özellik |
|---|---|
| Product | Forte AHF Panel — Active Harmonic Filter Cabinet |
| Frekans | 50 / 60 Hz |
| Bağlantı tipi | 3P3W and 3P4W |
| THDi target | < 5% at point of common coupling (PCC) |
| Compensation mode | Selective harmonic / broadband / combined with reactive |
| Communication | Modbus RTU + Ethernet + RS485 |
| HMI | 7″ / 10″ touch screen LCD with harmonic spectrum display |
| Auto-commissioning | One-button setup with automatic CT ratio detection |
| Protection | Integrated main breaker, surge protection, thermal monitoring |
| Current transformers | Built-in CTs (matched to cabinet capacity) |
| Enclosure rating | IP31 / IP42 / IP54 (configurable) |
| Soğutma | Forced fan cooling with smart speed control |
| Parallel operation | Multiple cabinets in parallel — linear capacity scaling |
| Factory testing | Full FAT before shipment |
| Standartlar | IEC 61000-3-4 / IEC 61439-1 / IEEE 519 |
Fabrikada test edilmiş, bağlantıya hazır komple harmonik azaltma çözümü — THDi değerlerini IEEE 519 ve IEC 61000 uyumluluk seviyelerine düşürür.
Karşı fazlı harmonik akım enjeksiyonu, ortak bağlantı noktasındaki toplam harmonik bozulmayı %5'in altına düşürür — tüm tesis tipleri için IEEE 519 ve IEC 61000-3-4 limitlerini karşılar.
Endüstriyel ortamlarda karşılaşılan tüm harmonik mertebelerini kapsar — 2. harmonikten (ark ocakları) 51. harmoniğe (yüksek frekanslı anahtarlama yükleri) kadar.
Her harmonik mertebe ayrı ayrı etkinleştirilebilir, devre dışı bırakılabilir veya önceliklendirilebilir. Sadece önemli harmonikleri hedefleyin — örneğin 5. ve 7.'yi önceliklendirip 11. ve 13.'yü izleyin.
Gerçek zamanlı harmonik spektrum gösterimi, filtreleme öncesi ve sonrası bireysel harmonik büyüklüklerini gösterir. Trend kaydı ve alarm geçmişi kabin ön panelinden erişilebilir.
Tek tuşla devreye alma, CT oranlarını otomatik algılar, mevcut harmonik profilini ölçer ve filtreleme önceliklerini yapılandırır. Kurulum süresini saatlerden dakikalara düşürür.
Birden fazla AHF Pano otomatik yük paylaşımı ve harmonik akım dağılımı ile paralel çalışır. Karmaşık sistem yeniden yapılandırması olmadan filtreleme kapasitesini doğrusal olarak ölçeklendirin.
Wherever non-linear loads generate harmonic distortion that exceeds utility limits or causes equipment interference.
Variable frequency drives are the largest source of harmonic distortion in modern industry. AHF Panels clean the bus at the MCC level.
UPS systems and server power supplies generate significant 5th and 7th harmonics. Critical infrastructure demands clean power.
Welding robots, servo drives and CNC machines create complex harmonic profiles requiring selective filtering.
Ultra-sensitive processes require THDi well below 5%. AHF Panels provide the clean power environment that production demands.
Large rectifier-fed DC drives for crushers and conveyors. High harmonic content at the 6-pulse and 12-pulse characteristic orders.
Process control instrumentation sensitivity. AHF Panels prevent harmonic-induced measurement errors and relay malfunctions.
LED lighting, IT equipment and elevator drives. Neutral conductor overloading from triplen harmonics in 3P4W systems.
Solar inverters and wind converters inject harmonics at the point of grid connection. Meet grid code requirements with active filtering.
Our engineering team will analyse your harmonic profile and size the correct filtering capacity — at no cost before commitment. Send us your power quality measurements.
Mühendislik ekibimiz 1 iş günü içinde sizinle iletişime geçecektir. Urgent: +90 850 840 64 24